Specifications

  • [Uc] Control Circuit Voltage: 110 V AC 50/60 Hz
  • [Ue] Rated Operational Voltage: power circuit <= 690 V AC 25…400 Hz || power circuit <= 300 V DC
  • Range Of Product: TeSys Deca
  • Contactor Application: resistive load || motor control
  • Product Or Component Type: contactor
  • Utilisation Category: AC-3 || AC-4 || AC-1 || AC-3e
  • [Ie] Rated Operational Current: 25 A 60 C) <= 440 V AC AC-1 power circuit || 12 A 60 C) <= 440 V AC AC-3 power circuit || 12 A 60 C) <= 440 V AC AC-3e power circuit
  • Poles Description: 3P
  • Device Short Name: LC1D

Contractual warranty

  • Warranty: 18 months

Complementary

  • Non-Overlap Time: 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
  • Minimum Switching Current: 5 mA signalling circuit
  • Power Dissipation Per Pole: 0.36 W AC-3 || 1.56 W AC-1 || 0.36 W AC-3e
  • Average Impedance: 2.5 mOhm – Ith 25 A 50 Hz power circuit
  • Auxiliary Contact Composition: 1 NO + 1 NC
  • [Ith] Conventional Free Air Thermal Current: 25 A 60 C power circuit || 10 A 60 C signalling circuit
  • Control Circuit Voltage Limits: 0.3…0.6 Uc -40-70 C drop-out AC 50/60 Hz || 0.8…1.1 Uc -40-60 C operational AC 50 Hz || 0.85…1.1 Uc -40-60 C operational AC 60 Hz || 1…1.1 Uc 60-70 C operational AC 50/60 Hz
  • Mounting Support: rail || plate
  • Contact Compatibility: M2
  • Control Circuit Type: AC 50/60 Hz standard
  • Safety Reliability Level: B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Pollution Degree: 3
  • Insulation Resistance: > 10 MOhm signalling circuit
  • Rated Breaking Capacity: 250 A 440 V power circuit IEC 60947
  • Irms Rated Making Capacity: 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Associated Fuse Rating: 10 A gG signalling circuit IEC 60947-5-1 || 40 A gG <= 690 V type 1 power circuit || 25 A gG <= 690 V type 2 power circuit
  • [Uimp] Rated Impulse Withstand Voltage: 6 kV IEC 60947
  • Inrush Power In Va: 70-70 VA 60 Hz 0.75 20 C) || 70-70 VA 50 Hz 0.75 20 C)
  • Pole Contact Composition: 3 NO
  • Connections – Terminals: power circuit screw clamp terminals 1 1-4 mm flexible without cable end || power circuit screw clamp terminals 2 1-4 mm flexible without cable end || power circuit screw clamp terminals 1 1-4 mm flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm flexible with cable end || power circuit screw clamp terminals 1 1-4 mm solid without cable end || power circuit screw clamp terminals 2 1-4 mm solid without cable end || control circuit screw clamp terminals 1 1-4 mm flexible without cable end || control circuit screw clamp terminals 2 1-4 mm flexible without cable end || control circuit screw clamp terminals 1 1-4 mm flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm flexible with cable end || control circuit screw clamp terminals 1 1-4 mm solid without cable end || control circuit screw clamp terminals 2 1-4 mm solid without cable end
  • Coil Technology: without built-in suppressor module
  • Operating Time: 12…22 ms closing || 4…19 ms opening
  • Minimum Switching Voltage: 17 V signalling circuit
  • Maximum Operating Rate: 3600 cyc/h 60 C
  • Signalling Circuit Frequency: 25…400 Hz
  • Tightening Torque: power circuit 1.7 N.m screw clamp terminals flat 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2
  • Electrical Durability: 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 12 A AC-3e <= 440 V
  • Mechanical Durability: 15 Mcycles
  • Auxiliary Contacts Type: mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Compatibility Code: LC1D
  • Hold-In Power Consumption In Va: 7.5-7.5 VA 60 Hz 0.3 20 C) || 7-7 VA 50 Hz 0.3 20 C)
  • Overvoltage Category: III
  • Maximum Horse Power Rating: 0.5 hp 115 V at AC 50/60 Hz for 1 phase || 2 hp 230/240 V at AC 50/60 Hz for 1 phase || 3 hp 200/208 V at AC 50/60 Hz for 3 phase || 3 hp 230/240 V at AC 50/60 Hz for 3 phase || 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase || 10 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Motor Power Kw: 3 kW 220…230 V AC 50/60 Hz AC-3) || 5.5 kW 380…400 V AC 50/60 Hz AC-3) || 5.5 kW 415…440 V AC 50/60 Hz AC-3) || 7.5 kW 500 V AC 50/60 Hz AC-3) || 7.5 kW 660…690 V AC 50/60 Hz AC-3) || 3.7 kW 400 V AC 50/60 Hz AC-4) || 3 kW 220…230 V AC 50/60 Hz AC-3e) || 5.5 kW 380…400 V AC 50/60 Hz AC-3e) || 5.5 kW 415…440 V AC 50/60 Hz AC-3e) || 7.5 kW 500 V AC 50/60 Hz AC-3e) || 7.5 kW 660…690 V AC 50/60 Hz AC-3e)
  • [Ui] Rated Insulation Voltage: power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Icw] Rated Short-Time Withstand Current: 105 A 40 C – 10 s power circuit || 210 A 40 C – 1 s power circuit || 30 A 40 C – 10 min power circuit || 61 A 40 C – 1 min power circuit || 100 A – 1 s signalling circuit || 120 A – 500 ms signalling circuit || 140 A – 100 ms signalling circuit
  • Heat Dissipation: 2-3 W 50/60 Hz
  • Protective Cover: with

Offer Sustainability

  • Rohs Exemption Information: Yes
  • Mercury Free: Yes
  • Environmental Disclosure: ENVPEP1501004
  • Sustainable Offer Status: Green Premium product
  • Pvc Free: Yes
  • Toxic Heavy Metal Free: Yes
  • Reach Regulation: Free of Substances of Very High Concern above the threshold
  • California Proposition 65: WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Reach Free Of Svhc: Yes
  • Weee: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • China Rohs Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
  • Circularity Profile: ENVEOLI1501004
  • Eu Rohs Directive: Compliant

Environment

  • Product Certifications: CCC || BV || CSA || GL || UL || RINA || GOST || LROS (Lloyds register of shipping) || DNV || UKCA
  • Height: 77 mm
  • Standards: CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Climatic Withstand: IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
  • Net Weight: 0.325 kg
  • Flame Retardance: V1 conforming to UL 94
  • Protective Treatment: THIEC 60068-2-30
  • Ip Degree Of Protection: IP20 front face IEC 60529
  • Mechanical Robustness: vibrations contactor open 2 Gn, 5…300 Hz) || vibrations contactor closed 4 Gn, 5…300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
  • Operating Altitude: 0…9842.52 ft (0…3000 m)
  • Fire Resistance: 850 C IEC 60695-2-1
  • Width: 45 mm
  • Depth: 86 mm
  • Permissible Ambient Air Temperature Around The Device: -40-60 C || 60-70 C with derating

Downloads

Spec Sheet

CAD

TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-bottom (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-isometric (dwg)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-back (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-right (dwg)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-top (dwg)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-top (dxf)
LC1D12F7_CAD_DOC – LC1D12F7_2D+Front+View (dwg)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-back (dwg)
LC1D12F7_CAD_DOC – LC1D12F7_2D+Right+Side+View (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-left (dxf)
LC1D12F7_CAD_DOC – LC1D12F7_2D+Front+View (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_3D-simplified (stp)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-left (dwg)
LC1D12F7_CAD_DOC – LC1D12F7_2D+Right+Side+View (dwg)
LC1D12F7_CAD_DOC – LC1D12F7_3D (stp)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-isometric (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-bottom (dwg)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-right (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-front (dxf)
TeSys Control Relay AC – 3D CAD – MCADPP0003369_2D-front (dwg)

Brochure

Industrial Automation and Control Product Lines Brochure – 998-20256927_2019_Line_Card_GM (pdf)
TeSys Refresh Informational Guide – Brochure – 998-20803955_GMA-US (pdf)
Square D Model 6 Intelligent Motor Control Centers Brochure – 8998BR0001 (pdf)

Technical Drawing

LC1D12F7_2DSalesDrawing_PDF – LC1D12F7_2D+Sales+Drawing (pdf)
IEC Contactor 9-12A 3P D-Line Technical drawings – E0200101-01 (pdf)
IEC Contactor 9-12A 3P D-Line Technical drawings – E0200101-01 (dxf)
IEC Contactor 9-12A 3P D-Line Technical drawings – E0200101-01 (dwg)

Catalog

Digest Catalog 18: Contactors and Starters-IEC (SEP 2022) – 0100CT1901_SEC-18_SEP2022 (pdf)

Circularity Profile

TeSys Deca Contactor 3P 09A AC – EoLI_ENVEOLI1501004_V4 (pdf)

Certificate

CSA Certificate_TeSys GV2ME&GV2RT&GV2P&GV2MC&GV2MP and GV2P Type E & GV2P combined with LC1D09-38 type F – COFC_80115485_EN (pdf)
UL_Certificate_TeSys GV2P Type E & GV2P combined with LC1D09-38 type F – E134347-20020916-CertificateofCompliance (pdf)
CB Certificate TeSys D – LC1D09-18&LC2D09-18_Batam plant – LC.D09-18_Batam_HU_003710_M1 (pdf)
UL_Certificate_TeSys D_LC1D09-38&LC2D09-38&LC1D098-128&LC1DT20-25&LC2DT20-25&LC1D188-258&LC1DT32-DT40&LC2DT32-DT40_DPE_AC coils and electronic coils – E48539-20001010-CertificateofCompliance (pdf)
CSA Certificate_TeSys D_LC1D09-38&LC2D09-38&LC1D098-128&LC1DT20-25&LC2DT20-25&LC1D188-258&LC1DT32-DT40&LC2DT32-DT40_DPE – COFC_80150207_EN (pdf)
CB Certificate TeSys D – LC1D09-18&LC2D09-18_Le Vaudreuil – LC.D09-18_LV_HU_003683_M1 (pdf)

Environmental Disclosure

TeSys Deca Contactor 3P 09A AC – Internal+PEP+ENVPEP1501004_V4 (pdf)

Instruction sheet

LC1D 9 to 38 A AC/DC contactors with screw clamp terminals – Instruction Sheet – 137830401A55-14 (pdf)
LC1D 9 to 38 A AC/DC contactors with screw clamp terminals – Instruction Sheet – 137832301A55-14 (pdf)

Declaration of conformity

EU RO MR Type Approval Certificate_TeSys D_LC1D09-38&LC2D09-38&LC1D098-128&LC1DT20-25&LC2DT20-25&LC1D188-258&LC1DT32-DT40&LC2DT32-DT40&CAD&LAD – LC.D09-38_LC.DT20-40_CAD_LAD_MRE000000F-rev1+(1) (pdf)
EU Declaration TeSys D -LC1D09-18&LC2D09-18 – PP_EU_Doc_LC.D09-18_SC16040407I.docx (pdf)
UKCA Declaration TeSysD_LC1D09-18&LC2D09-18 – UK_Doc_LC.D09-18_SC16040407B-UK.docx (pdf)

Data Bulletin

Motor Control Solutions for the North American Market Data Bulletin – 8536DB0901+R04_23 (pdf)

Videos

Locating the TeSys D Line IEC Contactor Model Number | Schneider Electric Support Mounting Auxiliary Contact Block to TeSys D Series Contactor | Schneider Electric Support Mounting & Unmounting TeSys D Contactors to DIN Rails | Schneider Electric Support Installing & Removing Mechanical and Electrical Interlock on TeSys D | Schneider Electric Support Removing Auxiliary Contact Block from TeSys D Series Contactor | Schneider Electric Support

Shipping Info Standard Shipping
Free Shipping We offer free shipping on orders over $30. Please check the free - shipping eligibility at checkout.
Delivery Time: It usually takes 3-5 business days for standard shipping. Please note that this is an estimated time frame and may be affected by local holidays, and unforeseen circumstances.